| Large Screen Display High Voltage Switch Action Characteristic Tester |
Technical Parameters:
Time test range: 1-499.9ms Resolution: 0.01ms Accuracy ≤0.1ms
Speed test range: 15ms Resolution: 0.01m/s Accuracy ±1% reading + 2 digits
Stroke test range: Unlimited Resolution: 0.01mm Accuracy ±1% reading + 2 digits
DC power supply selection range: 25-265V/10A Resolution: 1V Accuracy ≤±1%
Working power supply: AC220V ±10% Frequency: 50Hz ±5%
Ambient temperature: -10°C~40°C Relative humidity: ≤85%
Insulation resistance: ≤2MΩ
Dielectric strength: Power input to enclosure can withstand 1.5KV for 1 minute withstand voltage test.
Product Features:
Can perform electric operation and manual operation
Suitable for mechanical dynamic characteristic testing of various high-voltage circuit breakers within 500KV voltage level
Can measure actual stroke and custom stroke
Able to perform single close, single open, close-open, close-open-close, open-close-open operations of circuit breakers
Easy wiring, simple operation, only one close (open) action is needed to obtain all close (open) data, can choose to save 50 sets of data, provide later query and upload to computer for storage, also can view and print all data and motion curve graphs on site
Built-in clock circuit, can display current year, month, day, hour, minute, second, even if power off, can automatically save setting data and test data
Built-in delay protection function, after circuit breaker action, automatically cut off the action power supply, well protecting the circuit breaker equipment and high-voltage switch tester
The instrument has built-in DC power supply, selectable range: 30-270V/10A, no voltage drop at the moment of output of conventional rectifier power supply, very accurate for testing switch action voltage
Can dynamically analyze the relationship between stroke and speed of circuit breaker per 1ms time
Can be configured with upload software to achieve computer archiving and online viewing, printing.
Can test any type of circuit breaker
Safety Requirements:
1. Only qualified technicians should perform maintenance to prevent fire or personal injury.
2. Use appropriate power cord. Only use the power cord dedicated to this product and conforming to its specifications.
3. Connect and disconnect correctly. Do not arbitrarily connect or disconnect test leads when they are connected to live terminals.
4. Product grounding. In addition to grounding through the power cord ground wire, the grounding terminal of the product enclosure must be grounded. To prevent electric shock, the grounding conductor must be connected to the ground. Before connecting to the input or output terminals of this product, ensure that the product is properly grounded.
5. Pay attention to all terminal ratings. To prevent fire or electric shock hazard, pay attention to all ratings and markings of this product. Before connecting to this product, read the product instruction manual for further information on ratings.
6. Do not operate without instrument cover. Do not operate this product if the cover or panel is removed.
7. Use appropriate fuses. Only use fuses that meet the specified type and rating of this product.
8. Avoid contact with exposed circuits and live metal. Do not touch exposed contacts and parts when the product is energized.
9. Do not operate if there is a suspected fault. If the product is suspected to be damaged, have it inspected by maintenance personnel and do not continue operation.
10. After testing, wait for discharge to complete before removing test leads.
Large screen display high voltage switch mechanical characteristic tester, this instrument has built-in isolated adjustable DC power supply and switch operation command simulation control module. During the test, the internal DC power supply can directly control the switch opening, closing, and reclosing operations, with automatic or manual action voltage test function.
Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.![]()