| KITC-IV High Voltage Switch Mechanical Characteristics Tester Darui Electric recommends KITC-IV High Voltage Switch Mechanical Characteristics Tester Features: |
KITC-IV High Voltage Switch Mechanical Characteristics Tester Features:
1. 8.4-inch color large screen, Windows operating system, user-friendly interface, intuitive, touch screen, convenient for field operators.
2. High-speed thermal printer, convenient for on-site printing of test data.
3. Built-in integrated operating power supply, no need for external power supply on site, convenient and quick. Provides DC20~265V adjustable power supply, current 20A. Arbitrarily set the operating voltage value of opening and closing coils, and can perform low voltage operation test of circuit breaker.
4. Equipped with linear sensor, rotary sensor, universal sensor, bracket, special multifunctional connector, very easy and simple to install.
5. Suitable for all models of SF6 switches, GIS combined electrical appliances, vacuum switches, oil switches produced domestically and internationally.
6. One switch operation obtains all data and graphics.
7. The host can store 6000 sets of test data (expandable memory card), built-in real-time clock, convenient for archiving.
8. Equipped with USB interface, data can be directly saved to USB drive, uploaded to computer for analysis and storage.
9. Can measure 12 metal contact breaks and 6 closing resistors simultaneously.
10. Contains envelope curve, generates standard envelope curve through test values of multiple (2-10) switches for analysis and comparison, and can also perform switch vibration frequency analysis.
11. Internal anti-interference circuit can be reliably used in 500KV substations.
KITC-IV High Voltage Switch Mechanical Characteristics Tester Parameters:
1. Operating Environment
Input Power Supply 220V±10% 50Hz±10% Atmospheric Pressure 86~106kPa
Temperature -20~45℃ Humidity ≤80%RH
2. Safety Performance
Insulation Resistance >2MΩ
Dielectric Strength Power supply to chassis withstand 1.5KV for 1 minute, no flashover or arcing.
3. Basic Parameters
��Time: Range 16000.0ms Resolution 0.1ms Error ≤ 0.1%±1 ms
◆Speed: Range 20.00m/s Resolution 0.01m/s Error ≤ 1%±0.01 m/s
◆Travel:
| Range | Resolution | Error | |
| Vacuum Circuit Breaker | 50.0mm | 0.1mm | ≤1%±1mm |
| SF6 Circuit Breaker | 300.0mm | ||
| Oil Circuit Breaker | 1000.0mm |
◆Coil Current: Range 30.00A Resolution 0.01A Error ≤ 1%
◆Coil Resistance: Range 27.0KΩ Resolution 0.1Ω Error ≤ 1%
◆Output Power Supply: DC0~270V digitally adjustable/20A Resolution 1V Error ≤ 1%
◆Dimensions and Weight: 340mm(L)×240mm(W)×210mm(H) 10kg
Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.![]()