Containerized Load BankDarui Electric recommends for youProduct IntroductionMarine containerized load bank (ultra-high power intelligent load bank) Marine generators mostly use diesel fuel. When diesel runs below 50% load or under no load for a long time, it can cause incomplete combustion, carbon buildup, reduced overall efficiency, and eventually lead to starting difficulties, insufficient power, increased fuel consumption, and premature overhaul or scrapping. The load bank is an ideal dummy load for generators. The ALB-DT marine containerized load bank (ultra-high power intelligent load bank) is an ideal testing device for measuring generator parameters such as power, frequency, voltage, current, power factor, and stability.
The ALB-D intelligent three-phase AC load bank (diesel generator set test load bank) we provide can test the output power and load capacity of various generator sets.
Function Introduction1. Stainless steel fixed container design.
2. During acceptance of newly installed diesel generators, test whether they meet design requirements.
3. After adding noise reduction equipment such as mufflers to diesel generators, test whether their output power meets the operational needs of communication equipment.
4. After repairing diesel generators, test whether performance indicators such as output power and load capacity meet requirements.
5. Routine maintenance and periodic testing of diesel generators: according to the newly issued communication power maintenance regulations, diesel generators should be loaded and tested for 15-30 minutes every six months.
Application FieldsShips, railways, electric power, communication base station power supply load testing.
Main Technical Specifications Discharge Power 10KW 20KW 20KW 20KW 20KW
Discharge Voltage Range AC 400V/20V Three-phase Four-wire AC 400V/230V Three-phase Four-wire AC 300V Three-phase Four-wire AC 600V Three-phase Four-wire AC 10.5KV Three-phase Four-wire
Frequency Measurement Range 50HZ/60HZ 50HZ/60HZ 50HZ 50HZ 50HZ
Power Measurement Range 0-10kw 0-20kw 0-100kw 0-500kw 0-10kw
Adjustment Accuracy 1KW 0-20kw 1KW 1KW 1KW
Control Type AC Contactor AC Contactor High Voltage Vacuum Contactor High Voltage Vacuum Contactor High Voltage Vacuum Contactor
Power Supply Three-phase + N AC 380V Three-phase + N AC 380V Three-phase + N AC 380V Three-phase + N AC 380V Three-phase + N AC 380V
Protection Devices Overvoltage, High Temperature Alarm, Fan Fault Protection Overvoltage, High Temperature Alarm, Fan Fault Protection Overvoltage, High Temperature Alarm, Fan Fault Protection Overvoltage, High Temperature Alarm, Fan Fault Protection Overvoltage, High Temperature Alarm, Fan Fault Protection
Cooling Method Forced Air Cooling Forced Air Cooling Forced Air Cooling Forced Air Cooling Forced Air Cooling
Optional Functions Manual Type / Computer Remote Control
Voltage ± (0.25% of reading + 0.25% of range) ± (0.25% of reading + 0.25% of range) Optional Instrument Optional Instrument Optional Instrument
Current ± (0.25% of reading + 0.25% of range) ± (0.25% of reading + 0.25% of range)
Power Power Factor = 1.0: ± (0.25% of reading + 0.25% of range) Power Factor = 1.0: ± (0.25% of reading + 0.25% of range)
Running Time ±2 seconds per hour ±2 seconds per hour
Electric Energy Power Factor = 1.0: ± (0.25% of reading + 0.25% of range) Power Factor = 0.5: ± (0.5% of reading + 0.5% of range) Power Factor = 1.0: ± (0.25% of reading + 0.25% of range) Power Factor = 0.5: ± (0.5% of reading + 0.5% of range)
Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.