Generator Test Load Bank
Darui Electric recommends
Product Application: |
Power communication, China Unicom Mobile UL test switch standards
Railway Bureau Signal Section Generator maintenance UPS maintenance
Electrical switch test aging test, transformer test, charging pile load capacity
High Power Generator Test Load Bank IP-RLC Programmable AC Load Product Specifications
Model Mode IP-RLC30S IP-RLC60S IP-RLC120S IP-RLC200S IP-RLC300S IP-RLC600S IP-RLC1000S
Capacity Power 10K 30K 60K 120K 200K 300K 600K 1000K
Resistive Power 11.11KW 33.33KW 63.33KW 123.33KW 213.33KW 333.33KW 633.33KW 1233.33KW
Inductive Power 11.11KVA 33.33KVA 63.33KVA 123.33KVA 213.33KVA 333.33KVA 633.33KVA 1233.33KVA
Capacitive Power 11.11Kvar 33.33Kvar 63.33Kvar 123.33Kvar 213.33Kvar 333.33Kvar 633.33Kvar 1233.33Kvar
Phase A Resistive Power - 11.11KW 21.11KW 41.11KW 71.11KW 111.11KW 211.11KW 411.11KW
Inductive Power - 11.11KVA 21.11KVA 41.11KVA 71.11KVA 111.11KVA 211.11KVA 411.11KVA
Capacitive Power - 11.11Kvar 21.11Kvar 41.11Kvar 71.11Kvar 111.11Kvar 211.11Kvar 411.11Kvar
Phase B Resistive Power - 11.11KW 21.11KW 41.11KW 71.11KW 111.11KW 211.11KW 411.11KW
Inductive Power - 11.11KVA 21.11KVA 41.11KVA 71.11KVA 111.11KVA 211.11KVA 411.11KVA
Capacitive Power - 11.11Kvar 21.11Kvar 41.11Kvar 71.11Kvar 111.11Kvar 211.11Kvar 411.11Kvar
Phase C Resistive Power - 11.11KW 21.11KW 41.11KW 71.11KW 111.11KW 211.11KW 411.11KW
Inductive Power - 11.11KVA 21.11KVA 41.11KVA 71.11KVA 111.11KVA 211.11KVA 411.11KVA
Capacitive Power - 11.11Kvar 21.11Kvar 41.11Kvar 71.11Kvar 111.11Kvar 211.11Kvar 411.11Kvar
Regulation Precision Resistive: 0.001KW, Inductive: 0.001KVA, Capacitive: 0.001Kvar
Working Mode Resistive, inductive, and capacitive loads can be freely combined
Main Testing Items Can be used for the following tests: anti-islanding effect/efficiency test of grid-connected inverters, overload protection test, energy meter standard, switch test, UPS test and maintenance
Control Mode Touch screen control or PC control optional
Input Voltage Can be manufactured according to customer requirements
Supply Voltage 1φ2W, AC220V, 50HZ
Display Measurement Main measurement parameters: voltage, current, frequency, active power, reactive power, power factor, voltage and current harmonic content (optional)
Current Resolution 0.001A
Current Accuracy ±0.5%
Voltage Resolution 0.1V
Voltage Accuracy ±1%
Display Method LED display
Remote Control Interface 485/232C Ethernet communication
Cooling Mode Forced air cooling
Protection Over-temperature
Operating Temperature -10℃~+40℃
Weight (Kg) 180 250 450 800 1000 1100 1250 1400
Dimensions W×H×D (mm) 800*1500*700 800*1700*750 1000*1600*1000 1200*1600*1200 1200*1800*1200 1200*1800*1700 1400*1800*1700 1400*1800*2000
Note: Special specifications can be customized according to customer requirements. Dimensions and weight are subject to actual product.
Special specifications can be customized according to customer requirements (power, step, size, display, customized model with slightly longer circumference).
Ordering Selection Instructions: To facilitate customers in selecting our products, please provide the following parameters before ordering:
1. Rated voltage, 2. Rated power, 3. Power step requirement, 4. Operating conditions and environment, 5. Working mode (default long-term working mode)
Product Features:1. Controlled by touch screen + PLC, with local control and PC control modes, providing corresponding upper computer operation software.
2. Inductive, capacitive, and resistive load power can be arbitrarily combined. Resistive 0.001KW to maximum power adjustable, inductive 0.001KW to maximum power adjustable, capacitive 0.001KW to maximum power adjustable. Meets precise adjustment of AC resonance point under unbalanced three-phase voltage conditions.
3. According to performance parameter detection requirements, the discharge power can be arbitrarily combined and set through the operation panel.
4. Simulates resonance occurrence of AC electrical equipment, effectively and accurately detecting the anti-islanding protection function of grid-connected inverters.
5. Detects the working efficiency, maximum output power at full load, and load capacity of various inverters.
6. Simulates various complex working environments to test the comprehensive working performance of inverters under different conditions.
7. Resonance test: Set inductive power = capacitive power. During resonance, theoretically inductive and capacitive reactive power cancel each other out, reactive power = 0.
8. The minimum resolution of resistive load, inductive load, and capacitive load is 1W, which can accurately simulate AC resonance occurrence and meet the debugging and testing needs of inverters.
9. Can measure multiple data to meet inverter testing needs, including: resistive current, inductive current, capacitive current, voltage, current, frequency, power, apparent power, reactive power, total voltage harmonics, total current harmonics, power factor, voltage waveform. Measurement data can be uploaded to PC and realize process recording and storage of test data.
Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.