Partial Discharge DetectorDarui Electric recommends for youMain Technical Specifications 1. Capacitance range of test object: 6pF~250μF.
2. Detection sensitivity and allowable current
Input Unit
No. | Tuning Capacitance Range | Sensitivity (pC)
(Unbalanced Circuit) | Allowable Current (RMS) |
| Unbalanced Circuit | Balanced Circuit |
| 1 | 0 ~ 25 ~ 100pF | 0.02 | 30mA | 0.25A |
| 2 | 25 ~ 100 ~ 400pF | 0.04 | 50mA | 0.5A |
| 3 | 100 ~ 400 ~ 1500pF | 0.06 | 120mA | 1A |
| 4 | 400 ~ 1500 ~ 6000pF | 0.1 | 0.25A | 2A |
| 5 | 1500 ~ 6000 ~ 25000pF | 0.2 | 0.5A | 4A |
| 6 | 0.006 ~ 0.025 ~ 0.1μF | 0.3 | 1A | 8A |
| 7 | 0.025 ~ 0.1 ~ 0.4μF | 0.5 | 2A | 15A |
| 8 | 0.1 ~ 0.4 ~ 1.5μF | 1 | 4A | 30A |
| 9 | 0.4 ~ 1.5 ~ 6.0μF | 1.5 | 8A | 60A |
| 10 | 1.5 ~ 6.0 ~ 25μF | 2.5 | 15A | 120A |
| 11 | 6.0 ~ 25 ~ 60μF | 5 | 25A | 200A |
| 12 | 25 ~ 60 ~ 250μF | 10 | 50A | 300A |
| 7R | Resistor | 0.5 | 2A | 15A |
Table 1: Detection sensitivity and allowable current values for input units
3. Elliptical scanning time base
(1) Frequency: 50Hz;
(2) Rotation: in steps of 30°, can rotate 120°;
(3) Display mode: Ellipse - Straight line.
4. Display unit
Uses a 98×84 (mm) rectangular oscilloscope tube, with brightness and focus adjustment knobs.
5. Amplifier
(1) 3dB low-frequency cutoff: selectable 10, 20, 40kHz;
(2) 3dB high-frequency cutoff: selectable 80, 200, 300kHz;
(3) Gain adjustment: coarse adjustment 6 steps, gain difference between steps 20±1dB, fine adjustment range > 20dB;
(4) Asymmetry of positive and negative pulse response < 1dB.
6. Time window
(1) Window width: adjustable, 15°~150° at 50Hz;
(2) Window position: each window can be rotated 0°~170°;
(3) Two time windows can be opened separately or simultaneously.
7. Pulse peak meter
(1) Linear scale analog meter 0—100 error ±5% (of full scale).
(2) Logarithmic scale analog meter 0—10—100 error ±5% (of full scale).
(3) Digital meter: 3.5-digit LED display 0—100 error: ±3% (of full scale).
8. Test voltmeter
(1) Uses a 3.5-digit digital meter, can read test voltage or pC value;
(2) This system uses a capacitive voltage divider, 0~100kV direct reading;
(3) Error: ±3%.
9. Zero marking system
Internal peak marker generator produces peak markers (the PD detector must be connected to a 1000:1 capacitive voltage divider to generate them).
10. Calibration pulse generator (built-in)
(1) Calibration square wave voltage amplitude: 10mV~4V divided into 11 steps;
(2) Calibration square wave pulse rise time: ≤60nS;
(3) Calibration square wave pulse fall time: ≥100uS;
(4) Discharge calibration range (when high voltage injection capacitance is 100pF): 1, 2, 4, 5, 10, 20, 40, 50, 100, 200, and 400pC;
(5) Repetition frequency: same as time base frequency 50Hz;
(6) Pulse rotation: 0~360°, divided into two ranges.
This product is designed and developed by our factory specifically for partial discharge testing of cross-linked cables based on the characteristics of the cable industry. It has a built-in calibration pulse generator, higher integration, small size, and simple operation.
Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.