GKC-98 H5 High Voltage Switch Characteristic Tester
Darui Electric recommends
Technical Parameters
1. Operating Environment
Input Power: 220V±10% 50Hz±10% Atmospheric Pressure: 86~106kPa
Temperature: -10~40℃ Humidity: ≦80%RH
2. Safety Performance
Insulation Resistance: >2MΩ Dielectric Strength: Power supply to chassis withstand 1.5kV AC for 1 minute, no flashover or arcing.
3. Basic Parameters
Range: 4000.0ms Resolution: 0.1ms
Error: ① Within 100ms 0.1ms±1 digit
② Above 100ms 0.1%±1 digit
③ Synchronism
Speed: 20.00m/s Resolution: 0.01m/s
Error: ① Within 0-2m/s ±0.1m/s±1 digit
② Above 100ms ±0.2m/s±1 digit
Closing Resistor: 1600Ω Resolution: 1Ω
Stroke:
|
Range
|
Resolution
|
Error
|
Vacuum Circuit Breaker
|
50.0mm
|
0.1mm
|
1%±1 digit
|
SF6 Circuit Breaker
|
300.0mm
|
1mm
|
Low Oil Circuit Breaker
|
600.0mm
|
1mm
|
Current: 20.00A Resolution: 0.01A
Output Power: DC30~250V digitally adjustable/20A (instantaneous operation)
Dimensions: 360mm×280mm×300mm
Weight: 9kg
Features:
1. Suitable for mechanical characteristic testing of all models of SF6 switches, GIS combined electrical appliances, vacuum switches, and oil switches produced domestically and internationally.
2. Strong anti-interference capability; can easily test and measure even when the bypass bus of a 500kV substation is live.
3. Universal speed sensor, linear sensor, and rotary sensor are easy and quick to install.
4. One switch operation obtains all data and corresponding waveform graphs of the switch mechanical characteristics.
5. The host can store on-site test data, with a built-in real-time clock for archiving test date and time.
6. Large screen, wide temperature range, direct view, backlit LCD, full Chinese display of all data and graphs; LCD contrast electronically adjustable, power-off memory.
7. Chinese menu operation, easy to use. Built-in printer for quick printing of all data and graphs at any time.
8. Equipped with data analysis management software, can operate with PC; test results can be output to various dot matrix, laser, or inkjet printers for test reports, computerizing field tests.
Performance
1. Time: Inherent opening and closing time of 6 contacts, same-phase synchronism, inter-phase synchronism.
2. Reclosing: Close-Open, Open-Close, Open-Close-Open process time for each contact: opening time, first closing time, second closing time, metal short-circuit time, dead time.
3. Bounce: Closing bounce time, bounce count, bounce process, bounce waveform for each contact; opening rebound amplitude for each contact.
4. Speed: Instantaneous opening and closing speed, maximum speed, time-stroke characteristic curve.
5. Stroke: Total stroke, contact gap, overtravel, overshoot stroke, rebound amplitude.
6. Current: Opening and closing coil current values, current waveform.
7. Operating Voltage: Built-in DC30~250V/20A digitally adjustable circuit breaker operating power supply, automatically performs low voltage operation test, measures the operating voltage of the circuit breaker.
|