Technical Specifications:

Varistor Measurement
Technical SpecificationMeasurement RangeWorking ErrorTest Condition
Initial Action Voltage U1mA0~1999V≤±1%±1d1mA±5μA
Leakage Current I0.75U1mA0~199.9μA≤±2μA±1d0.75U1mA

≤±1%±1d

Discharge Tube Measurement

Technical SpecificationMeasurement RangeWorking ErrorTest Condition
DC Breakdown Voltage Vsdc5~1999V≤±1%±1dVoltage Rise Rate

100V/S±10%

Insulation Resistance: 6MΩ (500V)

Withstand Voltage:    AC  1.5kV  50HZ  1min

Operating Temperature and Humidity: 0~+40℃   ≤85%RH

Storage Temperature and Humidity: -10℃~+50℃   ≤90%RH

Power Supply: AC  220V   50Hz

DC  12V        0.5A    (Core wire + pole)

Power Consumption: 8W

Dimensions: 208mm×190mm×78mm

Weight: ≤1kg

Operation Panel:

1. Test Hole +            2. Test Hole -        3. Range Adjustment   

4. LCD Display          5. Voltage Preset         6. Single/Continuous Switch  

7. Function Selector Switch        8. High Voltage Indicator       9. High Voltage Start Button     

10. Display Conversion Button          11. Test Button          12. Discharge Indicator

13. Fuse Holder           14. Power Switch       15. Power Socket

16. External DC 12V Power Jack (Core wire is +)

Notes and Instructions:

1. This instrument is equipped with a range (test range) adjustment function. In use, it can reduce the test voltage as much as possible to reduce energy consumption, extend instrument life, and reduce safety hazards. It can also reduce test time and improve efficiency. It can be used for group screening and inspection discrimination. Users can fully and reasonably utilize this function.

Preset Voltage Adjustment Range:     0V ~ 1800V

Range Voltage Adjustment Range:    100V ~ 1999V

If the range setting or test value exceeds 1999V, the display shows an overflow signal "1".

2. The preset voltage value for discharge tube testing is the starting value of the 100V/S rate rising voltage and also the lower limit of the test range. The preset voltage for varistor testing is only used as the lower limit for judgment; the actual lower limit of the test range always starts from 0V.

3. The preset voltage should be set lower than the range upper limit voltage. Otherwise, the test voltage will be under the range (upper limit) control state. During varistor testing, a buzzer sound will indicate over-range after each test; during discharge tube testing, the green light will be repeatedly lit, accompanied by an over-range sound prompt. At this point, reducing the preset voltage will bring the high voltage back to the preset state.

4. The test voltage of this instrument can be as high as 2kV. Keep the panel, test leads, and work surface clean and dry to avoid test errors caused by leakage current, arcing, or corona.

5. A two-phase three-wire power socket must be used, and the ground wire should be properly grounded.

6. Operators should take necessary high-voltage protection measures to avoid electric shock.

Performance Features:

Vacuum Arrester Tester Discharge Tube Measuring Instrument, suitable for measuring DC parameters of overvoltage protection components such as zinc oxide arresters (varistors), metal-ceramic two- and three-electrode discharge tubes, and vacuum arresters. It can also be used as a stabilized voltage and constant current source for other applications.

Vacuum Arrester Tester Discharge Tube Measuring Instrument, features high-voltage short-circuit protection, overcurrent protection, high-voltage preset, range adjustment, etc., with a high-voltage self-discharge time of less than 0.5 seconds.

It has a self-test function.

Measurement data is displayed on a 3 1/2 LCD digital display, with high accuracy and good reliability.

During measurement, the range can be preset, and an audible prompt is given for over-range testing, suitable for component grouping and inspection discrimination.

Selecting continuous measurement allows for uninterrupted testing of batch samples.

Vacuum Arrester Tester Discharge Tube Measuring Instrument, with simple panel functions, easy to operate.

Lightweight and easy to carry.

Note: The above information and technical parameters are compiled and released by Yangzhou Dary Electric Co., Ltd.

WeChat QR Code
💬
💬 Message ✕

Hello! Have you found what you need? Contact us directly online!

Leave a Message for Consultation
Yangzhou Darui Electric Co., Ltd.
主营产品:Dielectric Loss Tester、Transformer Ratio测试仪、Loop Resistance Tester、高压None线核相仪、Insulation Resistance Tester、Partial Discharge Tester、Cable Fault Tester、DC Resistance Tester等。
☎ Tel: 18952707000(关经理)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com
Verification Code
By submitting, you agree to ourTerms of ServiceandPrivacy Policy
🏠 网站Home📞 一键拨号✉ Contact Us